2002-08-23 00:00:00DENIED:
  
 1. PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.
  
 2. PLEASE SIZE SUPPLY DUCT SERVING THE
 RESTROOMS.
  
 3. AS PER FBC(M) 606.2.2, WHERE MULTIPLE
 AIR HANDLING SYSTEMS SHARE COMMON
 SUPPLY OR RETURN AIR DUCTS OR PLENUMS
 WITH A COMBINED DESIGNED CAPACITY
 GREATER THAN 2,000 CFM, THE RETURN &
 SUPPLY AIR SYSTEM SHALL BE PROVIDED
 WITH SMOKE DETECTORS IN ACCORDANCE
 WITH SECTION 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.