| Plan Review Notes For Permit 02080376 |
| Permit Number |
02080376 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-23 00:00:00 | DENIED: | | | | | | 1. PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89. | | | | | | 2. PLEASE SIZE SUPPLY DUCT SERVING THE | | | RESTROOMS. | | | | | | 3. AS PER FBC(M) 606.2.2, WHERE MULTIPLE | | | AIR HANDLING SYSTEMS SHARE COMMON | | | SUPPLY OR RETURN AIR DUCTS OR PLENUMS | | | WITH A COMBINED DESIGNED CAPACITY | | | GREATER THAN 2,000 CFM, THE RETURN & | | | SUPPLY AIR SYSTEM SHALL BE PROVIDED | | | WITH SMOKE DETECTORS IN ACCORDANCE | | | WITH SECTION 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|