Plan Review Notes
Plan Review Notes For Permit 02080364
Permit Number 02080364
Review Stop R
Sequence Number 2
Notes
Date Text
2002-11-06 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SEE ENGINEERING ANALYSIS AND REVISE
 THE DIAPHRAGM SCHEDULE AS REQUIRED.
 **ALSO, REVISE THE SPECS ON THE WALL
 SECTIONS/DETAILS TO MATCH ENGINEERING
 ANALYSIS.
 2-STORM SHUTTERS: A)DESIGN PRESSURES
 SPECIFIED HAVE LIMITATIONS ON PANEL
 SPAN. SEE DESIGN PRESSURES CALCULATED
 BY ARCHITECT AND REVISE AS REQUIRED.
 B)MARK ON DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED.
 3-REVISE DETAIL 11/S3. NEED ONE HR FIRE
 RATED ASSEMBLY CONSIDERING EXPOSURE TO
 FIRE ON THE EXTERIOR AND INTERIOR SIDE
 AS REQ'D BY TABLE 600 FOOTNOTE I.
 4-NO INFORMATION WAS GIVEN ON THE SIZE
 OF ANCHOR BOLTS TO BE USED AT BOTTOM
 PLATE OF STEEL COLUMN. DETAIL 41/S2
 REFERS TO COLUMN SCHEDULE, BUT THERE
 IS NO INFORMATION GIVEN ON THE COLUMN
 SCHEDULE. PROVIDE INFORMATION AS REQ'D