| 2002-11-06 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-SEE ENGINEERING ANALYSIS AND REVISE | | | THE DIAPHRAGM SCHEDULE AS REQUIRED. | | | **ALSO, REVISE THE SPECS ON THE WALL | | | SECTIONS/DETAILS TO MATCH ENGINEERING | | | ANALYSIS. | | | 2-STORM SHUTTERS: A)DESIGN PRESSURES | | | SPECIFIED HAVE LIMITATIONS ON PANEL | | | SPAN. SEE DESIGN PRESSURES CALCULATED | | | BY ARCHITECT AND REVISE AS REQUIRED. | | | B)MARK ON DRAWINGS SPECIFIC MOUNTING | | | CONDITIONS AND ANCHOR TYPE AND SPACING | | | TO BE USED. | | | 3-REVISE DETAIL 11/S3. NEED ONE HR FIRE | | | RATED ASSEMBLY CONSIDERING EXPOSURE TO | | | FIRE ON THE EXTERIOR AND INTERIOR SIDE | | | AS REQ'D BY TABLE 600 FOOTNOTE I. | | | 4-NO INFORMATION WAS GIVEN ON THE SIZE | | | OF ANCHOR BOLTS TO BE USED AT BOTTOM | | | PLATE OF STEEL COLUMN. DETAIL 41/S2 | | | REFERS TO COLUMN SCHEDULE, BUT THERE | | | IS NO INFORMATION GIVEN ON THE COLUMN | | | SCHEDULE. PROVIDE INFORMATION AS REQ'D |
|