| Plan Review Notes For Permit 02080362 |
| Permit Number |
02080362 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-10-28 00:00:00 | APPROVED WITH PROVISO: | | | 1-STRUCTURAL PLANS TO MATCH ENGINEER'S | | | CALCULATIONS. SEE ENGINEER'S REPORT | | | FOR SIZE OF FASTENERS USED FOR SHEAR | | | CALCULATIONS. | | | 2-CLARIFY SIZE OF FOOTING. SEE FOOTING | | | SCHEDULE AND ALL WALL SECTIONS. THE DO | | | NOT MATCH. | | | 3-PROVIDE PRODUCT APPROVAL FOR EXTERIOR | | | SWING SIDE DOOR AT GARAGE. | | | 4-REVISE STORM SHUTTERS INSTALLATION | | | SCHEDULE: A)CLARIFY DESIGN PRESSURES. | | | SEE ARCHITECTURAL DWGS. B)CLARIFY | | | TYPE OF ANCHOR TO BE USED: RAWL OR | | | CAULK-IN. C)MARK ANCHOR TYPE & SPACING | | | SPACING ON STORM SHUTTERS INSTALLATION | | | SCHEDULE OF STORM SHUTTERS DRAWINGS. |
|