| Plan Review Notes For Permit 02080330 |
| Permit Number |
02080330 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-05 00:00:00 | HOLDING APPLICATION IN MY OFFICE PENDING | | | AIC RATING AND AFFIRMATION OF PANEL | | | FEEDER SIZE,DRAWING HAS #3'S@ 125 | | | AMPS,ONLY GOOD FOR 110 | | | AMPS/310-15(B)(6). | | | | | | WRT |
|