| Plan Review Notes For Permit 02080312 |
| Permit Number |
02080312 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-09-05 00:00:00 | DENIED:MECHANICAL PERMIT 02080314 | | | | | | 1.PROVIDE ENERGY & SIZING CALCULATIONS | | | IN ACCORDANCE WITH 2001 FBC CHAPTER | | | 13 SECTION 407. | | | | | | 2.PROVIDE OUTSIDE AIR CALCS AS PER | | | 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89. | | | | | | 3.PLEASE INDICATE LINE SIZE & PIPING | | | FOR THE LIQUID, SUCTION & CONDENSATE | | | PLEASE NOTE AS PER 2001 FBC 1503.4.4 | | | CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12 INCHES AWAY FROM THE BUILDING | | | STRUCTURE. | | | | | | 4.PLANS INDICATE DUCT SERVING THE 1ST | | | FLOOR. WILL BOTH FLOORS BE OCCUPIED | | | BY THE SAME TENANT? | | | | | | 5.PLANS INDICATE A GARAGE DOOR ON THE | | | FIRST FLOOR PLEASE INDICATE WHAT THE | | | OCCUPANY TYPE IS FOR THE 1ST & 2ND | | | FLOOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|