Plan Review Notes For Permit 02080312
Permit Number 02080312
Review Stop M
Sequence Number 1
Notes
Date Text
2002-09-05 00:00:00DENIED:MECHANICAL PERMIT 02080314
  
 1.PROVIDE ENERGY & SIZING CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC CHAPTER
 13 SECTION 407.
  
 2.PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.
  
 3.PLEASE INDICATE LINE SIZE & PIPING
 FOR THE LIQUID, SUCTION & CONDENSATE
 PLEASE NOTE AS PER 2001 FBC 1503.4.4
 CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12 INCHES AWAY FROM THE BUILDING
 STRUCTURE.
  
 4.PLANS INDICATE DUCT SERVING THE 1ST
 FLOOR. WILL BOTH FLOORS BE OCCUPIED
 BY THE SAME TENANT?
  
 5.PLANS INDICATE A GARAGE DOOR ON THE
 FIRST FLOOR PLEASE INDICATE WHAT THE
 OCCUPANY TYPE IS FOR THE 1ST & 2ND
 FLOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.