| Plan Review Notes For Permit 02080312 |
| Permit Number |
02080312 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-15 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE COMMENTS FROM FIRE | | | PLAN REVIEW THAT WILL HAVE A DIRECT | | | AFFECT ON THE ELECTRICAL PLANS. | | | EXITS/EM/LTS. | | | | | | 2)NOTE: PLEASE NOTE THAT SQ. FT NEEDS | | | TO BE SHOWN IN LOAD CALCULATIONS, | | | 220-3,220-10,,,,,, | | | | | | | | | | | | 3)NOTE: PLEASE NOTE THAT THE MIN OF 125% | | | IS SHOWN FOR AHU ON LOAD CALCULATIONS, | | | BUT HAS A 2P-50A BRKR IN PANEL FOR OCP? | | | PLEASE CLARIFY | | | | | | 4)NOTE: PLEASE NOTE THAT AREA FOR AHU | | | AND HWH DOES NOT SEEM TO MEET CLEARENCE | | | REQUIREMENTS FOR COMBUSTIBLES. PLEASE | | | ALSO NOTE IT DOES NOT SEEM THE OPENING | | | IS LARGE ENOUGH BETWEEN WALL AND AHU | | | TO REPLACE HWH IF NECCESARY.?? | | | PLEASE VERIFY. 110-26, 424-13 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|