Plan Review Notes
Plan Review Notes For Permit 02080312
Permit Number 02080312
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-15 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SEE COMMENTS FROM FIRE
 PLAN REVIEW THAT WILL HAVE A DIRECT
 AFFECT ON THE ELECTRICAL PLANS.
 EXITS/EM/LTS.
  
 2)NOTE: PLEASE NOTE THAT SQ. FT NEEDS
 TO BE SHOWN IN LOAD CALCULATIONS,
 220-3,220-10,,,,,,
  
  
  
 3)NOTE: PLEASE NOTE THAT THE MIN OF 125%
 IS SHOWN FOR AHU ON LOAD CALCULATIONS,
 BUT HAS A 2P-50A BRKR IN PANEL FOR OCP?
 PLEASE CLARIFY
  
 4)NOTE: PLEASE NOTE THAT AREA FOR AHU
 AND HWH DOES NOT SEEM TO MEET CLEARENCE
 REQUIREMENTS FOR COMBUSTIBLES. PLEASE
 ALSO NOTE IT DOES NOT SEEM THE OPENING
 IS LARGE ENOUGH BETWEEN WALL AND AHU
 TO REPLACE HWH IF NECCESARY.??
 PLEASE VERIFY. 110-26, 424-13
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372