| 2002-08-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) GREASE TRAP SHALL BE SIZED BY THE |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE |
| | CONTACT RODNEY COMPO @ (561) 837-4074 |
| | UTILITY ORD #2938-96 |
| | 2) SHT C-5A GREASE/WATER SEPARATOR DE- |
| | TAIL, INFLUENT & EFFLUENT C/O'S SHALL BE |
| | 2-WAY C/O'S. |
| | 3) SHT P7 GREASE TRAP DETAIL, SEE ATTACH |
| | ED WPB UTILITY APPROVED GREASE TRAP DE- |
| | TAIL. |
| | 4) BACKFLOW REQUIRED ON WATER SERVICE. |
| | (SEE SHT P6 WATER SERVICE DETAIL) |
| | PLUMBING CONTRACTOR SHALL CUT IN TEE AND |
| | INSTALL VALVE FOR IRRIGATION CONTRACTOR |
| | IF SEPARATE BACKFLOW IS NOT INSTALLED AT |
| | METER. |
| | 5) SHT P1, ALL INDIRECT WASTE SHALL BE |
| | DRAINED TO A FLOOR SINK, NOT TO FLOOR |
| | DRAINS. (SEE FREEZER/COOLER, ICE MACHINE |
| | SODA DISPENSER ECT) |
| | 6) SHT P2, WATER FILTER SHALL BE NSF |
| | APPROVED. PLEASE PROVIDE MANUF. INFO. |
| | 7) SHT P2, WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS SHALL BE INSTALLED PER |
| | 604.9 AT ALL QUICK CLOSING VALVES. (ICE |
| | MACHINES, WASH MACHINES, ECT.) ARRESTORS |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT AT THE TOP OF DROP |
| | PDI-WH 201 AND MANUF INSTALLATION INSTR- |
| | UCTIONS. |
| | 8) SHT P6 WATER HEATER DETAIL, BOTTOM |
| | FED WATER HEATERS SHALL HAVE A VACUUM |
| | RELIEF VALVE INSTALLED. SEC 504.2 |
| | 9) SHT P6 WATER HEATER DETAIL, THE DIS- |
| | CHARGE LINE FROM THE P/T RELIEF VALVE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE |
| | WATER HEATER. |
| | 10) SHT P6 HUB DRAIN NOT APPROVED, FLOOR |
| | SINK REQD FOR INDIRECT WASTE PER SEC |
| | 802.3. PLEASE DELETE DETAIL. |
| | 11) SHT P7 FUNNEL FLOOR DRAIN NOT APP- |
| | ROVED. PLEASE DELETE DETAIL. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |