Plan Review Notes
Plan Review Notes For Permit 02080275
Permit Number 02080275
Review Stop P
Sequence Number 1
Notes
Date Text
2002-08-26 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) GREASE TRAP SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT RODNEY COMPO @ (561) 837-4074
 UTILITY ORD #2938-96
 2) SHT C-5A GREASE/WATER SEPARATOR DE-
 TAIL, INFLUENT & EFFLUENT C/O'S SHALL BE
 2-WAY C/O'S.
 3) SHT P7 GREASE TRAP DETAIL, SEE ATTACH
 ED WPB UTILITY APPROVED GREASE TRAP DE-
 TAIL.
 4) BACKFLOW REQUIRED ON WATER SERVICE.
 (SEE SHT P6 WATER SERVICE DETAIL)
 PLUMBING CONTRACTOR SHALL CUT IN TEE AND
 INSTALL VALVE FOR IRRIGATION CONTRACTOR
 IF SEPARATE BACKFLOW IS NOT INSTALLED AT
 METER.
 5) SHT P1, ALL INDIRECT WASTE SHALL BE
 DRAINED TO A FLOOR SINK, NOT TO FLOOR
 DRAINS. (SEE FREEZER/COOLER, ICE MACHINE
 SODA DISPENSER ECT)
 6) SHT P2, WATER FILTER SHALL BE NSF
 APPROVED. PLEASE PROVIDE MANUF. INFO.
 7) SHT P2, WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE INSTALLED PER
 604.9 AT ALL QUICK CLOSING VALVES. (ICE
 MACHINES, WASH MACHINES, ECT.) ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF DROP
 PDI-WH 201 AND MANUF INSTALLATION INSTR-
 UCTIONS.
 8) SHT P6 WATER HEATER DETAIL, BOTTOM
 FED WATER HEATERS SHALL HAVE A VACUUM
 RELIEF VALVE INSTALLED. SEC 504.2
 9) SHT P6 WATER HEATER DETAIL, THE DIS-
 CHARGE LINE FROM THE P/T RELIEF VALVE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER.
 10) SHT P6 HUB DRAIN NOT APPROVED, FLOOR
 SINK REQD FOR INDIRECT WASTE PER SEC
 802.3. PLEASE DELETE DETAIL.
 11) SHT P7 FUNNEL FLOOR DRAIN NOT APP-
 ROVED. PLEASE DELETE DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377