| Plan Review Notes For Permit 02080220 |
| Permit Number |
02080220 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-09-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) ONLY THE FIXTURES WITHIN THE BATHROOM | | | GROUPS SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN.SEC 909.1 | | | ANY ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. - THE LAUN- | | | DRY TRAY SHALL BE TIED IN DOWNSTREAM OF | | | THE VENT LINE FOR THE WATER CLOSET. SEE | | | RED LINE ON SHEET 1 SUBMITTED. | | | 2) SANITARY RISER DIAGRAM SHALL REFLECT | | | THE FLOOR PLAN. IF THE BLDG DRAIN IS | | | ENTERING THE BLDG FROM THE FRONT THEN | | | THE MASTER BATH SHALL BE SHOWN ON THE | | | RIGHT SIDE OF BLDG DRAIN AND BATH #2 ON | | | THE LEFT SIDE OF THE BLDG DRAIN TO RE- | | | FLECT FLOOR PLAN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|