| 2002-12-03 00:00:00 | REVIEW COMMENTS SUBJECT TO 1997 SBCCI |
| | |
| | THE WINDOW OPENING PROPOSED ON THE WEST |
| | SIDE IS PROHIBITTED BY SBC TABLE 600. |
| | SEE EXTERIOR WALLS 0'-3' FROM A |
| | PROPERTY LINE.PLEASE REVISE AS |
| | NECESSARY AND ENSURE THREE HOUR RATED |
| | CONSTRUCTION. |
| | |
| | THE FIRST FINANCIAL SURVEYORS SHOWS THIS |
| | WALL 1'-6" BEYOND THE PROPERTY LINE. |
| | IS THERE AN EXISTING PARTY OR FIRE WALL |
| | AS DEFINED IN SBC 202 TO PROVIDE |
| | SEPARATE BUILDINGS? |
| | |
| | THE NEW CONSTRUCTION FOR THE VESTIBULE |
| | ON THE SOUTH, (ALLEY SIDE) IS REQUIRED |
| | TO BE OF TYPE V CONSTRUCTION, |
| | (NON-COMBUSTIBLE) AND TWO HOUR FIRE |
| | RATED.SEE SBC 607 AND SBC TABLE 600. |
| | |
| | SHEET A1 SHOWS ONE AND FOUR INCH DOOR |
| | THRESHOLD HEIGHTS WHICH DO NOT COMPLY |
| | WITH THE MAXIMUM 1/2" ALLOWED BY THE |
| | 1997 FACBC 4.13.8 FOR ENTRANCE DOORS. |
| | |
| | THE WALLS OF THE PROPOSED SECOND STORY |
| | ARE REQUIRED TO BE OF NON-COMBUSTIBLE |
| | CONSTRUCTION.SEE FBC 607.THE USE OF |
| | PLYWOOD SHEATHING AND WOOD TOP PLATES |
| | DOES NOT COMPLY.ALSO, WALLS LOCATED |
| | 10'-20' FROM A PROPERTY LINE ARE |
| | REQUIRED TO BE OF TWO HOUR FIRE RATED |
| | CONSTRUCTION. SEE SBC TABLE 600 FOR TYPE |
| | V ONE HOUR PROTECTED.THE FLOOR TRUSS |
| | CONFIGURATION SHOWN IN DETAIL 3/A5 DOES |
| | NOT COMPLY WITH THE EXTERIOR WALL |
| | REQUIREMENTS OF TYPE V CONSTRUCTION. |
| | |
| | SHOW THE DRAFTSTOPPING IN ACCORDANCE |
| | WITH SBC 2305.2.2 FOR THE FLOOR CEILING |
| | AND ROOF CEILING ASSEMBLIES. |
| | |
| | SEE THE 8/29/02 COMMENTS RE: IMPACT |
| | FEES AND PRODUCT APPROVALS. |