2002-12-03 00:00:00REVIEW COMMENTS SUBJECT TO 1997 SBCCI
  
 THE WINDOW OPENING PROPOSED ON THE WEST
 SIDE IS PROHIBITTED BY SBC TABLE 600.
 SEE EXTERIOR WALLS 0'-3' FROM A
 PROPERTY LINE.PLEASE REVISE AS
 NECESSARY AND ENSURE THREE HOUR RATED
 CONSTRUCTION.
  
 THE FIRST FINANCIAL SURVEYORS SHOWS THIS
 WALL 1'-6" BEYOND THE PROPERTY LINE.
 IS THERE AN EXISTING PARTY OR FIRE WALL
 AS DEFINED IN SBC 202 TO PROVIDE
 SEPARATE BUILDINGS?
  
 THE NEW CONSTRUCTION FOR THE VESTIBULE
 ON THE SOUTH, (ALLEY SIDE) IS REQUIRED
 TO BE OF TYPE V CONSTRUCTION,
 (NON-COMBUSTIBLE) AND TWO HOUR FIRE
 RATED.SEE SBC 607 AND SBC TABLE 600.
  
 SHEET A1 SHOWS ONE AND FOUR INCH DOOR
 THRESHOLD HEIGHTS WHICH DO NOT COMPLY
 WITH THE MAXIMUM 1/2" ALLOWED BY THE
 1997 FACBC 4.13.8 FOR ENTRANCE DOORS.
  
 THE WALLS OF THE PROPOSED SECOND STORY
 ARE REQUIRED TO BE OF NON-COMBUSTIBLE
 CONSTRUCTION.SEE FBC 607.THE USE OF
 PLYWOOD SHEATHING AND WOOD TOP PLATES
 DOES NOT COMPLY.ALSO, WALLS LOCATED
 10'-20' FROM A PROPERTY LINE ARE
 REQUIRED TO BE OF TWO HOUR FIRE RATED
 CONSTRUCTION. SEE SBC TABLE 600 FOR TYPE
 V ONE HOUR PROTECTED.THE FLOOR TRUSS
 CONFIGURATION SHOWN IN DETAIL 3/A5 DOES
 NOT COMPLY WITH THE EXTERIOR WALL
 REQUIREMENTS OF TYPE V CONSTRUCTION.
  
 SHOW THE DRAFTSTOPPING IN ACCORDANCE
 WITH SBC 2305.2.2 FOR THE FLOOR CEILING
 AND ROOF CEILING ASSEMBLIES.
  
 SEE THE 8/29/02 COMMENTS RE: IMPACT
 FEES AND PRODUCT APPROVALS.