Plan Review Notes
Plan Review Notes For Permit 02080218
Permit Number 02080218
Review Stop P
Sequence Number 1
Notes
Date Text
2002-08-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT D-1 ALL CAPPED OFF PLUMBING SHALL
 BE INSPECTED PRIOR TO COVERING.
 2) SHT SP-2 FOUNTAIN SHALL HAVE A SEPAR-
 ATE PERMIT. WILL THERE BE A DRAIN AND/0R
 WATER HOOK UP TO THE FOUNTAIN?
 3) SHT A-1 DRINKING FOUNTAIN SHALL BE A
 HIGH/LOW OR OTHER PROVISIONS SHALL MADE
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. 11-4.1.3(10)(A)
 4) SHT A-1 PER TABLE 403.1 A SERVICE
 SINK IS REQUIRED.
 5) SHT A-1 RESIDENTIAL UNITS, 1 AUTOMAT-
 IC CLOTHES WASHER CONNECTION PER DWELL-
 ING PER TABLE 403.1 - ALSO SHT A-2
 6) SHT A-6 ACCESSIBLE TOILET ROOM DETAIL
 SHOW 2'10" (34") TO FLOOD RIM OF LAV.
 SEC 11-4.19.2
 7) SHTS P-1 FLOOR PLAN AND P-3 SANITARY
 RISER DIAGRAM, PLUMBING FROM THE FUTURE
 TENANT SPACE AND SECOND FLOOR UNITS
 SHALL NOT DRAIN THROUGH THE WET VENTED
 BATHROOM ON THE FIRST FLOOR. SEC 909.1
 8) SHTS P-1 FLOOR PLAN AND P-3 SANITARY
 RISER DIAGRAM, SINK SHALL NOT DRAIN THRU
 WET VENTED TOILET ROOM IN OFFICE SPACE
 SEC 909.1. FLOOR DRAIN SHALL BE TAKEN
 OFF THE VENTED LINE.
 9) SHT P-2 PLUMBING SPECIFICATIONS #2
 CODE REFERENCE SHALL BE FBC-2001 PLUMB-
 ING NOT STANDARD CODE.
 10) BACKFLOW REQUIRED ON WATER SERVCICE.
 11) WATER RISER DIAGRAM REQUIRED FOR
 RESIDENTIAL UNITS. WATER HAMMERS ARREST-
 ORS ARE REQUIRED FOR ALL QUICK CLOSING
 VALVES PER 604.9 LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE". ARRESTORS
 REQUIRED FOR ICE MACHINE, DISHWASHERS,
 AND WASH MACHINES ECT. - REQUIRED FOR
 1ST FLOOR OFFICE WATER RISER ALSO.
 12) SHT P-3 WATER HEATERS, THE RELIEF
 VALVE DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHALL HAVE A VISIB-
 LE AIR GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM. 504.7.1
 13) THERMAL EXPANSION CONTROL FOR WATER
 HEATERS PER 607.3.2. PROVIDE DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377