2002-09-13 00:00:00DENIED:
  
 PLEASE NOTE, PLANS REVIEWED IN
 ACCORDANCE WITH 2001 FBC.REVISE PLANS
 TO INDICATE CURRENT CODE INSTEAD OF THE
 1997 SBC.
  
 PLAN SHEET M-1 - PLEASE CLARIFY LOCATION
 OF C.U. 1 & 3, IT APPEARS THEY MAY
 INTERFERE WITH ACCESS TO THE STORAGE
 AREA & DOORS.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 PROVIDE ENERGY AND MANUAL J CALCS AS
 PER CHAPTER 13 OF THE FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.