| 2002-09-13 00:00:00 | DENIED: | | | | | | PLEASE NOTE, PLANS REVIEWED IN | | | ACCORDANCE WITH 2001 FBC.REVISE PLANS | | | TO INDICATE CURRENT CODE INSTEAD OF THE | | | 1997 SBC. | | | | | | PLAN SHEET M-1 - PLEASE CLARIFY LOCATION | | | OF C.U. 1 & 3, IT APPEARS THEY MAY | | | INTERFERE WITH ACCESS TO THE STORAGE | | | AREA & DOORS. | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | | AREA BEING VENTILATED) OR TABLE 403.3 | | | FOR MECHANICAL VENTILATION. | | | | | | PROVIDE ENERGY AND MANUAL J CALCS AS | | | PER CHAPTER 13 OF THE FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|