Plan Review Notes
Plan Review Notes For Permit 02080218
Permit Number 02080218
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-08-29 00:00:001) WRONG BUILDING CODE REFERENCED.
 SHOULD READ FLORIDA BUILDING CODE 2000
 EDITION NOT THE STANDARD BUILDING CODE
 1997 EDITION.
  
 2) PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 3) DO THE AIR CONDITIONING SYSTEM
 UNITS INTERFERE WITH EXIT DISCHARGE
 FROM THE STAIRS.
  
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910