| 2002-08-27 00:00:00 | ************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE MISSING EGRESS LIGHTING |
| | IN BEDROOMS PER 210-70. PLEASE NOTE |
| | THAT PLANS SHOW FAN ONLY. PLEASE CLARIFY |
| | |
| | 2)NOTE: PLEASE NOTE MISSING COUNTERSPACE |
| | OUTLET PER 210-52-C-1UNIT-F |
| | |
| | 3)NOTE: PLEASE NOTE MISPRINT OF METER |
| | BANK #2 AS HOUSE PANEL AND HOUSE PANEL |
| | AS METER BANK. |
| | |
| | 4)NOTE: PLEASE NOTE ARC FAULT PROTECTION |
| | PER 210-12. PLEASE LIST ON PANEL |
| | SCHEDULES. |
| | |
| | 5)NOTE: PLEASE NOTE SQ FOOTAGE NEEDS TO |
| | BE SHOWN FOR EACH APT UNIT AND FOR EACH |
| | COMM SPACE IN LAOD CALCULATIONS. PER |
| | 220-3,220-10,220-13 ECT |
| | PLEASE CLARIFY HOW EACH APT IS THE SAME |
| | AT 800 SQ FT? PLEASE CLARIFY NO SQ FT |
| | SHOWN FOR COMM UNITS. |
| | CLARIFY BOTH FUTURE UNITS SHOWN AS SAME |
| | SQ FT? |
| | CLARIFY HOW LOAD IS FIGURED FOR COMM |
| | AREAS IN RESIDENTIAL LOAD CALCULATIONS. |
| | |
| | 6)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS BLDG STEEL TO BE APART OF |
| | GROUNDING ELECTRODE SYSTEM. PLEASE |
| | CLARIFY IF EXISTING FOOTER IS GOING TO |
| | BE CUT/CHIPPED OUT TO MEET THIS? PLEASE |
| | NOTETHAT CODE REQ`S FOOTER STEEL ONLY |
| | WHEN EXPOSED AT NEW CONSTRUCTION. 250-50 |
| | PLEASE NOTE , IF SHOWN ON RISER THEN IT |
| | WILL BE REQ`D. JUST A NOTE. |
| | |
| | 7)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | PLEASE NOTE THAT EM LTS AND OR EXITS |
| | MAY BE REQ`D FOR WORK AREAS OF RES USE? |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |