Plan Review Notes
Plan Review Notes For Permit 02080218
Permit Number 02080218
Review Stop E
Sequence Number 1
Notes
Date Text
2002-08-27 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE MISSING EGRESS LIGHTING
 IN BEDROOMS PER 210-70. PLEASE NOTE
 THAT PLANS SHOW FAN ONLY. PLEASE CLARIFY
  
 2)NOTE: PLEASE NOTE MISSING COUNTERSPACE
 OUTLET PER 210-52-C-1UNIT-F
  
 3)NOTE: PLEASE NOTE MISPRINT OF METER
 BANK #2 AS HOUSE PANEL AND HOUSE PANEL
 AS METER BANK.
  
 4)NOTE: PLEASE NOTE ARC FAULT PROTECTION
 PER 210-12. PLEASE LIST ON PANEL
 SCHEDULES.
  
 5)NOTE: PLEASE NOTE SQ FOOTAGE NEEDS TO
 BE SHOWN FOR EACH APT UNIT AND FOR EACH
 COMM SPACE IN LAOD CALCULATIONS. PER
 220-3,220-10,220-13 ECT
 PLEASE CLARIFY HOW EACH APT IS THE SAME
 AT 800 SQ FT? PLEASE CLARIFY NO SQ FT
 SHOWN FOR COMM UNITS.
 CLARIFY BOTH FUTURE UNITS SHOWN AS SAME
 SQ FT?
 CLARIFY HOW LOAD IS FIGURED FOR COMM
 AREAS IN RESIDENTIAL LOAD CALCULATIONS.
  
 6)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS BLDG STEEL TO BE APART OF
 GROUNDING ELECTRODE SYSTEM. PLEASE
 CLARIFY IF EXISTING FOOTER IS GOING TO
 BE CUT/CHIPPED OUT TO MEET THIS? PLEASE
 NOTETHAT CODE REQ`S FOOTER STEEL ONLY
 WHEN EXPOSED AT NEW CONSTRUCTION. 250-50
 PLEASE NOTE , IF SHOWN ON RISER THEN IT
 WILL BE REQ`D. JUST A NOTE.
  
 7)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 PLEASE NOTE THAT EM LTS AND OR EXITS
 MAY BE REQ`D FOR WORK AREAS OF RES USE?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372