| Plan Review Notes For Permit 02080203 |
| Permit Number |
02080203 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-27 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) STRUCTURE IS LOCATED IN AN 'AO' FLOOD | | | ZONE AN ELEVATION CERTIFICATE IS | | | REQUIRED. | | | | | | 2) NO UPLIFT OR CONNECTORS ARE INDICATED | | | ON THE ROOF FRAMING PLAN ON SHEET 3A. | | | THE ANCHOR SCHEDULE SPECIFIES CONNECTORS | | | TO BE USED UNLESS OTHERWISE NOTED ON THE | | | FRAMING PLAN. IF THE REACTION VALUES | | | GIVEN ON THE TRUSS DRAWINGS EXCEED THE | | | CONNECTOR VALUES LISTED IN THE SCHEDULE, | | | A REVISED ROOF FRAMING PLAN WILL BE | | | REQUIRED. | | | | | | 3)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - ARCHED TOP FIXED GLASS WINDOW AS SHOWN | | | ON REAR ELEVATION. | | | - STORM PANELS(THE KEY PLAN AND INSTALL- | | | ATION SCHEDULE DID NOT HAVE A PRODUCT | | | APPROVAL WITH THEM) |
|