| Plan Review Notes For Permit 02080187 |
| Permit Number |
02080187 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-27 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) STRUCTURE IS LOCATED IN AN 'AO' FLOOD | | | ZONE, AN ELEVATION CERTIFICATE IS | | | REQUIRED. | | | | | | 2)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR ARCHED TOP FIXED GLASS | | | WINDOW AS SHOWN ON THE REAR ELEVATION. | | | | | | 3) NO UPLIFT VALUES OR CONNECTORS ARE | | | INDICATED ON THE ROOF FRAMING PLAN ON | | | SHEET 3. THE NOTE ON THE ANCHOR SCHEDULE | | | SPECIFIES THE ANCHORS TO BE USED UNLESS | | | OTHERWISE NOTED ON FRAMING PLAN. IF THE | | | VALUES GIVEN ON THE TRUSS DRAWINGS | | | EXCEED THOSE LISTED IN THE ANCHOR | | | SCHEDULE A REVISED FRAMING PLAN WILL BE | | | REQUIRED TO BE SUBMITTED FOR REVIEW. |
|