| Plan Review Notes For Permit 02080120 |
| Permit Number |
02080120 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-23 00:00:00 | PLUMBING PLAN REVIEW. DENIED FBC 2001 | | | 1) FBC-2001424.2.6.6.5 WHERE PROVIDED | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | 2) FBC-2001424.2.6.6.4 MINIMUM OF TWO | | | SUCTION INLETS SHALL BE PROVIDED FOR EA | | | PUMP. SEPARATED BY A MINIMUM OF 3 FEET | | | OR LOCATED ON TWO DIFFERENT PLANES. | | | (DETAIL) | | | 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT | | | PROTECTION FOR SUCTION INLETS. (DETAIL) | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X 8233 |
|