| Plan Review Notes For Permit 02080120 |
| Permit Number |
02080120 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-08 00:00:00 | PLUMBING PLAN REVIEW, DENIED FBC 2001 | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | 1) FBC-2001 424.2.7.2 PUMPS AND EQUIP- | | | MENT SHALL BE MOUNTED ON A SUBSTANTIAL | | | BASE IN A MANNER THAT WILL ELIMINATE | | | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- | | | AL 4" THICK. (DETAIL) | | | 3) FBC-2001 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 4) FBC-2001424.2.6.6.5 WHERE PROVIDED | | | THE VACUUM OR PRESSURE CLEANER FITTING | | | SHALL BE LOCATED AT LEAST 6" AND NOT | | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | | THE SKIMMER. | | | 5) FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | | ORD. #2853-95, BACKFLOW REQUIRED ON | | | WATER SERVICE. (ADD TO NOTES) | | | 6) FBC-2001 424.2.13.2JOINTS AND CON- | | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | | NOTES) | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|