2002-11-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 9/5/02:
  
 2) SHEET S3, DESIGN DATA NOTE 9 STILL
 STATES A DESIGN WIND SPEED OF 110 MPH.
 UNDER FLORIDA BUILDING CODE THE BASIC
 WIND SPEED FOR THE CITY OF WEST PALM
 BEACH IS 140 MPH (REF: FBC* 1606.1.6).
 AMEND THE PLANS.NOTE THAT FBC 1606.1.7
 REQUIRES THAT THE BASIC WIND SPEED,
 IMPORTANCE FACTOR, AND WIND EXPOSURE
 CATEGORY ALL BE STATED ON THE PLANS.
  
 7) THE DOOR AND WINDOW SCHEDULES ON
 SHEET A2 REFER TO THE SLIDING GLASS DOOR
 AS 'PGT WINGUARD IMPACT APPROVED DOORS'
 AND THE SINGLE HUNG WINDOWS AS
 'WINGUARD/33, .../DBL23 AND .../24'.
 THESE PRODUCTS HAVE REFERENCES WHICH ARE
 DIFFERENT TO THE SUBMITTED PRODUCT
 APPROVALS AND ARE THEREFOR NOT COVERED
 BY THOSE APPROVALS.AMEND THE SCHEDULES
 OR SUBMIT RELEVANT PRODUCT APPROVALS.
  
 12) FBC* 104.2.1.2TRUSS ANCHORS.THE
 FACT THAT THE UPLIFTS ARE GIVEN IN THE
 TRUSS SHOP DRAWING NOTES IS ACKNOWLEDGED
 THE ROOF FRAMING PLAN ON SHEET S2, SHALL
 BE AMENDED TO SHOW THE UPLIFT AND THE
 CONNECTOR MARK (ANCHOR REFERENCE), FROM
 THE ANCHOR SCHEDULE ON SHEET S3, FOR
 EACH TRUSS OR GROUP OF TRUSSES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499