Plan Review Notes
Plan Review Notes For Permit 02080117
Permit Number 02080117
Review Stop B
Sequence Number 1
Notes
Date Text
2002-09-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SHEET S3 REFERS TO STANDARD BUILDING
 CODE.AMEND PLANS TO REFER TO FLORIDA
 BUILDING CODE 2001, INCLUDING TIMBER AND
 WOOD NOTE 4, WOOD FRAMING NOTE 2, DESIGN
 DATA NOTES 8 AND 9.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORM.THE FOLLOWING INFORMATION SHALL
 BE COMPLETED ON THE SUBMITTED FORM:
 CLIMATE ZONE IS 8, ENTER BUILDER'S
 NAME, ENTER PERMITTING OFFICE AS WEST
 PALM BEACH, ENTER PERMIT NO. AS
 02080117, ENTER JURISDICTION NO. AS
 604700
  
 4) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) THE SUBMITTED PRODUCT APPROVALS ARE
 FOR THE SINGLE HUNG WINDOWS AND SLIDING
 GLASS DOOR ONLY.SUBMIT TWO COPIES OF
 PRODUCT APPROVALS FOR THE ROOFING,
 FRENCH DOORS, GLASS BLOCK WINDOWS AND
 A MULLION FOR DEN REAR WINDOW (SEE
 COMMENT 6, BELOW).
  
 6) SINGLE HUNG WINDOW PRODUCT APPROVAL
 NOA# 01-0109.01. THE SPECIFIC CONDITIONS
 ITEM 3.1 ON PAGE 2 STATES THAT THE
 PRODUCT APPROVAL APPLIES TO SINGLE UNIT
 APPLICATIONS ONLY.SUBMIT A PRODUCT
 APPROVAL APPLICABLE TO THE MULLED
 WINDOWS AT THE REAR OF THE DEN.
  
 7) THE DOOR AND WINDOW SCHEDULES ON
 SHEET A2 REFER TO THE SLIDING GLASS DOOR
 AS PGT WINGUARD IMPACT APPROVED DOORS,
 AND THE SINGLE HUNG WINDOWS AS
 WINGUARD/33, .../DBL23 AND .../24. THESE
 REFERENCES DO NOT CORRESPOND TO THE
 SUBMITTED PRODUCT APPROVALS.AMEND THE
 SCHEDULES.
  
 8) SHEET A3 - ELEVATIONS, STATES THAT
 THE EXISTING WINDOWS ARE TO REMAIN BUT
 THIS DOES NOT CORRELATE WITH SHEET A2 -
 FLOOR PLAN, WHICH REFERS TO THE EXISTING
 WINDOWS AS WINDOW SCHEDULE MARK B.
  
 9) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 SHOWER DOOR AND FRENCH DOORS (NOTE:
 DOOR SCHEDULE REFERS TO BATHROOM
 DOOR 'MARK 2' AS A FRENCH DOOR,
 SHOULD THIS REFERENCE BE FOR
 EXTERIOR DOOR 'MARK 5' INSTEAD?)
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
 WITH THE REQUIREMENT FOR SAFETY GLAZING.
  
 10) FBC 2309.6ATTIC ACCESS.AMEND THE
 PLANS TO SHOW AN ACCESS, TO THE ADDITION
 ATTIC, NOT LESS THAN 20"X36" OPENING.
  
 11) FBC* TABLE 2306.1ROOF SHEATHING
 NAILING SCHEDULE ON SHEET S2 SHOULD
 READ:
 ZONE 1&2: 8D COMMON @ 6"O.C. EDGES
 6"O.C. INTERMED.
 ZONE 3: 8D COMMON @ 4"O.C. EDGES
 6"O.C. INTERMED.
 AMEND SCHEDULE TO DEMONSTRATE COMPLIANCE
  
 12) FBC* 104.2.1.2TRUSS ANCHORS.ADD
 UPLIFT MAGNITUDES TO SHEET S2 - ROOF
 FRAMING PLAN AT TRUSS AND BEAM SUPPORTS.
  
 13) SHEET S2, DETAIL 3.THE NOTE
 SPECIFIES 4-1/2" DIA J-BOLTS.AMEND THE
 SECTIONAL VIEW TO SHOW TWO ROWS OF BOLTS
 TO CORRELATE WITH THE NOTE.
  
 14) SHEET A4, DETAIL 1 - FILLED CELL
 REINFORCEMENT.ANNOTATE THE PLANS TO
 SHOW THE #5 VERTICAL BARS TO HAVE MIN.
 25" LAP WITH THE FOOTING DOWEL AND MIN.
 OF A STANDARD HOOK WITH 10" LONG LEG
 EMBEDDED 6' INTO THE TIE BEAM.
  
 15) FBC 1007.4.2NEW STAIR RISERS AT
 THE LAUNDRY ROOM.THE DOOR SHALL NOT
 SWING OVER THE STAIR.
  
 16) SHEET S1 - FOUNDATION PLAN.THE
 COLUMNS IN THE COVERED DECK AREA SHOULD
 BE C-3 NOT C-1.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499