| 2002-08-12 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRETIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 3} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 4} PLEASE SHOW THE PANEL LOCATION ON THE |
| | PLANS. |
| | |
| | 5} PLEASE NOTE TWO APPLIANCE CIRCUITS |
| | REQUIRED FOR CALCS AND ON PANEL |
| | SCHEDULE PER 210-11(C)(1). |
| | |
| | 6} PLEASE CHECK THE RANGE CALCULATION |
| | FOR COMPLIANCE WITH TABLE 220-19,ALSO |
| | NOTE THE OCP SEEMS INCORRECT FOR THE |
| | LOAD SERVED. |
| | |
| | 7} THE GROUNDING ELECTRODE SYSTEM IS NOT |
| | COMPLETE PER 250-50 (ENTIRE ARTICLE). |
| | |
| | 8} PLEASE INDICATE THE CONDUIT AND WIRE |
| | TYPE AND SIZE ON THE SERVICE RISER. |
| | |
| | 9} THE GARAGE RECEPTACLES MUST COMPLY |
| | WITH 210-8(A)(2),PLEASE INDICATE SAME |
| | ON PLANS. |
| | |
| | 10} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ'D PER 210-52E. |
| | |
| | 11} NOTE RECEPTACLE SPACING IN THE |
| | BEDROOM MUST COMPLY WITH 210-52(A)(1). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL: |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/659-8096 EXT. 8093 |