2002-08-12 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRETIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE SHOW THE PANEL LOCATION ON THE
 PLANS.
  
 5} PLEASE NOTE TWO APPLIANCE CIRCUITS
 REQUIRED FOR CALCS AND ON PANEL
 SCHEDULE PER 210-11(C)(1).
  
 6} PLEASE CHECK THE RANGE CALCULATION
 FOR COMPLIANCE WITH TABLE 220-19,ALSO
 NOTE THE OCP SEEMS INCORRECT FOR THE
 LOAD SERVED.
  
 7} THE GROUNDING ELECTRODE SYSTEM IS NOT
 COMPLETE PER 250-50 (ENTIRE ARTICLE).
  
 8} PLEASE INDICATE THE CONDUIT AND WIRE
 TYPE AND SIZE ON THE SERVICE RISER.
  
 9} THE GARAGE RECEPTACLES MUST COMPLY
 WITH 210-8(A)(2),PLEASE INDICATE SAME
 ON PLANS.
  
 10} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52E.
  
 11} NOTE RECEPTACLE SPACING IN THE
 BEDROOM MUST COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8093