| | BUILDING PLAN REVIEW |
| | PERMIT: 02080087 |
| | ADD: 720 PALM STREET |
| | CONT:O/B PLAYER, JOHN |
| | TEL: (561)833-4811 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1) 104.1.1 WHEN REQUIRED, PERMIT. |
| | PERMITS ARE REQUIRED WHEN EVER THERE IS |
| | A CHANGE OF USE. CITY RECORDS INDICATE |
| | THE REAR UNIT BEING A GARAGE/ STORAGE |
| | USEAGE. TO CHANGE THE OF USE TO A GARAGE |
| | APT. SHALL REQUIRE PLANS TO BE REVIEWED |
| | BY THE COUNTY BUILDING DEPARTMENT FOR |
| | IMPACT ASSESSMENT. TO BE COMPLETED BY |
| | THE O/B. |
| | THE COUNTY PROPERTY APPRAISERS OFFICE |
| | INDICATES THERE IS NO REAR BUILDING, |
| | WHENEVER THERE IS A CHANGE OF USE |
| | GARAGE TO APT. THERE WILL SHOW SQ.FT. |
| | NUMBER OF ROOMS,ETC. THIS ALSO MEANS |
| | THERE IS NO TAXES BEING COLLECTED ON THE |
| | REAR UNIT. |
| | IT IS UP TO THE OWNER TO PROVE THAT |
| | THEIR WAS A PERMIT PULLED TO CHANGE THE |
| | OCCUPANCY FROM GARAGE/ STORAGE TO A |
| | APARTMENT. |
| | THE OWNER MAY CONTACT APRIL PICCIRILLO |
| | AT 659-8096 X 8292 RECORD RESEARCH FOR |
| | AN APPOINTMENT, THE OWNERS ACTUALLY SET |
| | WITH THE JOURNALS TO REVIEW IF A PERMIT |
| | WAS PULLED TO CHANGE OCC. FROM STORAGE |
| | TO RESIDENTIAL. |
| | |
| | 2) CHANGE OF OCCUPANCY. 3401.2.2 |
| | IF THE OCCUPANCY CLASSIFICATION OR OCCU- |
| | PANCY SUBCLASSIFICATIONS OF ANY EXISTING |
| | BUILDING OR STRUCTURE IS CHANGED, THE |
| | BUILDING, ELECTRICAL, PLUMBING, GAS & |
| | MECHANICAL SYSTEMS SHALL BE MADE TO |
| | CONFORM TO THE INTENT OF THE TECHNICAL |
| | CODES AS REQUIRED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 3) THE PERMIT APPLICATION INDICATES A |
| | VALUE OF $5,000.00 FOR THE COMPLETE |
| | PROJECT. THIS VALUE IS TO REFLECT THE |
| | MARKET VALUE. CITY CODE DOES ALLOW FOR |
| | IHE CITY TO DO A CALCULATED VALUE IF THE |
| | APPLICATION VALUE IS TO LOW. |
| | ORDANCE 3555-00.CHAP 7 SEC 7.2 FEE |
| | SCHEDULE. OWNER / BUILDER TO UP THE |
| | VALUE OF PERMIT TO MARKET VALUE. |
| | |
| | 4)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. |
| | |
| | 5)1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | TABLE 600 FOOTNOTE I BUILDINGS LOCATED |
| | LESS THAN 5'-0" FROM THE PROPERTY LINE. |
| | 709.6.2.2 THE FIRE RESISTANCE RATING OF |
| | A WOOD FRAMED ASSEMBLY IS EQUAL TO THE |
| | SUM OF THE TIME ASSIGNED TO THE MEMBRANE |
| | ON THE FIRE EXPOSED SIDE, THE TIME |
| | ASSIGNED TO THE FRAMING MEMBERS AND THE |
| | TIME ASIGNED FOR ADDITIONAL CONTRIBUTION |
| | BY OTHER PROTECTIVE MEASURES SUCH AS |
| | INSULATION. THE MEMBRANE ON THE |
| | UNEXPOSED SIDE SHALL NOT BE INCLUDED IN |
| | DETERMINING THE FIRE RESISTANCE OF THE |
| | ASSEMBLY. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |