2002-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SERVICE SINK REQUIRED PER TABLE
 403.1
 2) SHT 3.1 DOOR FROM CLOSET ROOM #111
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE FOR BREAK ROOM SINK.
 3)SHT 8.1 DETAIL #1 LUNCHROOM SINK SHALL
 COMPLY COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS.
 4) SHT P-2 FLOOR SINK SHOWN ON SANT.
 RISER DIAGRAM BUT NOT ON FLOOR PLAN.
 PLEASE CLAIRFY.
 5) PLEASE PROVIDE DETAIL FOR DRINKING
 FOUNTAIN. SHOW COMPLIANCE WITH 11-4.15
 AND ALL SUBSECTIONS. PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. 11-4.1.3(10)(A).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377