| Notes |
| Date |
Text |
| 2002-08-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SERVICE SINK REQUIRED PER TABLE | | | 403.1 | | | 2) SHT 3.1 DOOR FROM CLOSET ROOM #111 | | | SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE FOR BREAK ROOM SINK. | | | 3)SHT 8.1 DETAIL #1 LUNCHROOM SINK SHALL | | | COMPLY COMPLY WITH 11-4.24 AND ALL SUB- | | | SECTIONS. | | | 4) SHT P-2 FLOOR SINK SHOWN ON SANT. | | | RISER DIAGRAM BUT NOT ON FLOOR PLAN. | | | PLEASE CLAIRFY. | | | 5) PLEASE PROVIDE DETAIL FOR DRINKING | | | FOUNTAIN. SHOW COMPLIANCE WITH 11-4.15 | | | AND ALL SUBSECTIONS. PROVISIONS SHALL BE | | | MADE FOR THOSE WHO HAVE DIFFICULTY BEND- | | | ING OR STOOPING. 11-4.1.3(10)(A). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|