Plan Review Notes
Plan Review Notes For Permit 02071922
Permit Number 02071922
Review Stop FS
Sequence Number 1
Notes
Date Text
2002-08-01 00:00:001) DO PARKING SPACES BLOCK THE FIRE
 DEPARTMENT CONNECTIONS. ALL FIRE
 DEPARTMENT CONNECTIONS AND FIRE
 PROTECTION DEVICES SHALL HAVE AT
 LEAST SEVEN AND HALF FEET CLEARANCE TO
 THE FRONT AND SIDES OF THEM.
  
 2) NOTES ON PLANS SEEM TO CONTRADICT
 THE DRAWINGS. BATHROOMS AND CLOSETS
 APPEAR TO BE FIRE SPRINKLER PROTECTED
 BUT THE NOTES SUGGEST THE EXCEPTION
 TO THE CODE. PLEASE ADVISE.
  
 3) EXTERIOR FIRE SPRINKLERS SHALL BE
 CORROSION RESISTANT.
  
 4) IS THE LOFT BREEZEWAY THE SAME AS
 THE THIRD FLOOR BREEZEWAY.
  
 5) ARCHITECTURAL SOFFITS SHALL NOT
 INTERFERE WITH THE OPERATION OF
 ANY FIRE SPRINKLER HEADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved