| Plan Review Notes For Permit 02071922 |
| Permit Number |
02071922 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-01 00:00:00 | 1) DO PARKING SPACES BLOCK THE FIRE | | | DEPARTMENT CONNECTIONS. ALL FIRE | | | DEPARTMENT CONNECTIONS AND FIRE | | | PROTECTION DEVICES SHALL HAVE AT | | | LEAST SEVEN AND HALF FEET CLEARANCE TO | | | THE FRONT AND SIDES OF THEM. | | | | | | 2) NOTES ON PLANS SEEM TO CONTRADICT | | | THE DRAWINGS. BATHROOMS AND CLOSETS | | | APPEAR TO BE FIRE SPRINKLER PROTECTED | | | BUT THE NOTES SUGGEST THE EXCEPTION | | | TO THE CODE. PLEASE ADVISE. | | | | | | 3) EXTERIOR FIRE SPRINKLERS SHALL BE | | | CORROSION RESISTANT. | | | | | | 4) IS THE LOFT BREEZEWAY THE SAME AS | | | THE THIRD FLOOR BREEZEWAY. | | | | | | 5) ARCHITECTURAL SOFFITS SHALL NOT | | | INTERFERE WITH THE OPERATION OF | | | ANY FIRE SPRINKLER HEADS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|