2002-08-01 00:00:001) DO PARKING SPACES BLOCK THE FIRE
 DEPARTMENT CONNECTIONS. ALL FIRE
 DEPARTMENT CONNECTIONS AND FIRE
 PROTECTION DEVICES SHALL HAVE AT LEAST
 SEVEN AND HALF FEET CLEARANCE TO THE
 FRONT AND SIDES OF THEM.
  
 2) NOTES ON PLANS SEEM TO CONTRADICT
 THE DRAWINGS. BATHROOMS AND CLOSETS
 APPEAR TO BE FIRE SPRINKLER PROTECTED
 BUT THE NOTES SUGGEST THE EXCEPTION
 TO THE CODE. PLEASE ADVISE.
  
 3) EXTERIOR FIRE SPRINKLERS SHALL BE
 CORROSION RESISTANT.
  
 4) IS THE LOFT BREEZEWAY THE SAME AS
 THE THIRD FLOOR BREEZEWAY.
  
 5) ARCHITECTURAL SOFFITS SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY
 FIRE SPRINKLER HEADS.
  