2002-08-01 00:00:001) DO PARKING SPACES BLOCK THE FIRE
 DEPARTMENT CONNECTIONS. ALL FIRE
 DEPARTMENT CONNECTIONS AND FIRE
 PROTECTION DEVICES SHALL HAVE AT
 LEAST SEVEN AND HALF FEET CLEARANCE
 TO THE FRONT AND SIDES OF THEM.
  
 2) NOTES ON PLANS SEEM TO CONTRADICT
 THE DRAWINGS. BATHROOMS AND CLOSETS
 APPEAR TO BE FIRE SPRINKLER PROTECTED
 BUT THE NOTES SUGGEST THE EXCEPTION
 TO THE CODE. PLEASE ADVISE.
  
 3) EXTERIOR FIRE SPRINKLERS SHALL BE
 CORROSION RESISTANT.
  
 4) IS THE LOFT BREEZEWAY THE SAME AS THE
 THIRD FLOOR BREEZEWAY.
  
 5) ARCHITECTURAL SOFFITS SHALL
 NOT INTERFERE WITH THE OPERATION OF
 ANY FIRE SPRINKLER HEADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL