2002-08-01 00:00:001) THE FIRE DEPARTMENT SPRINKLER
 CONNECTION FOR THE CLUBHOUSE SHALL NOT
 EXCEED 150 FEET TO A FIRE HYDRANT. ALSO
 THE LOCATION OF THE FIRE DEPARTMENT
 CONNECTION APPEARS TO BE CONTRARY
 TO THE MAIN ENTRANCE AND THE FIRST
 FIRE HYDRANT THAT IS NEAREST THE
 CLUBHOUSE. PLEASE ADJUST AS NECESSARY.
  
 2) ALL FIRE DEPARTMENT CONNECTIONS AND
 POST INDICATOR VALVES SHALL BE
 PROVIDED WITH SEVEN AND HALF FEET
 CLEARANCES IN FRONT AND TO THE SIDES
 OF THEM.
  
 3) BACKFLOW DEVICES ARE REQUIRED TO BE
 EQUIPPED WITH TAMPER SWITCHES, CHAINS
 AND LOCKS.
  
 4) THE COVERED WALK NEAR THE GATHERING
 AREA APPEARS TO BE OVER FOUR FEET
 WIDE. IF THIS COVERED WALK IS
 COMBUSTIBLE FIRE SPRINKLER PROTECTION
 IS REQUIRED.
  
 5) ALL EXTERIOR SPRINKLER HEADS SHALL
 BE CORROSION RESISTANT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL