| Plan Review Notes For Permit 02071919 |
| Permit Number |
02071919 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-01 00:00:00 | 1) THE FIRE DEPARTMENT SPRINKLER | | | CONNECTION FOR THE CLUBHOUSE SHALL NOT | | | EXCEED 150 FEET TO A FIRE HYDRANT. ALSO | | | THE LOCATION OF THE FIRE DEPARTMENT | | | CONNECTION APPEARS TO BE CONTRARY | | | TO THE MAIN ENTRANCE AND THE FIRST | | | FIRE HYDRANT THAT IS NEAREST THE | | | CLUBHOUSE. PLEASE ADJUST AS NECESSARY. | | | | | | 2) ALL FIRE DEPARTMENT CONNECTIONS AND | | | POST INDICATOR VALVES SHALL BE | | | PROVIDED WITH SEVEN AND HALF FEET | | | CLEARANCES IN FRONT AND TO THE SIDES | | | OF THEM. | | | | | | 3) BACKFLOW DEVICES ARE REQUIRED TO BE | | | EQUIPPED WITH TAMPER SWITCHES, CHAINS | | | AND LOCKS. | | | | | | 4) THE COVERED WALK NEAR THE GATHERING | | | AREA APPEARS TO BE OVER FOUR FEET | | | WIDE. IF THIS COVERED WALK IS | | | COMBUSTIBLE FIRE SPRINKLER PROTECTION | | | IS REQUIRED. | | | | | | 5) ALL EXTERIOR SPRINKLER HEADS SHALL | | | BE CORROSION RESISTANT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|