2002-09-10 00:00:00FAILED :
 1. PLEASE SHOW THE LOCATION OF BACKFLOW
 PREVENTER ASSEMBLY AND CONNECTION TO
 CITY WATER SUPPLY, MUST BE INSTALLED AT
 POINT OF SERVICE ON PRIVATE PROPERTY,
 APPROVED BY THE CITY, 659-8005 EXT.2008.
 2. PLEASE SHOW LOCATION AND CONNECTION
 TO CITY SEWER SYS. A CLEAN OUT ON
 LATERAL MUST BE PROVIDED.
 3. A SEPARATE BACKFLOW PREVENTER FOR
 IRRIGATION SYS IS RECOMMENDED.
 4. ALL CONNECTION TO THE CITY SERVICES
 MUST BE PER CITY STANDARDS, 659-8040.
 5. TEMPORARY HOLDING TANKS AND WELL
 WATER IF USED WOULD REQUIRE PERMITS FROM
 PALM BEACH COUNTY HEALTH DEPARTMENT.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096