| Notes |
| Date |
Text |
| 2002-08-22 00:00:00 | DENIED | | | PROVIDE FULL PLANS AND INFORMATION ON | | | HOOD. HOOD SHALL BE UL LISTED (PROVIDE | | | SPECIFICS) OR ENGINEERED TO COMPLY WITH | | | NFPA 96 AND 1997 SMC. | | | PROVIDE INFORMATION ON DUCT WORK | | | INCLUDING SHAFT IF STRUCTURE IS | | | UNPROTECTED CONSTRUCTION. | | | PLANS INCLUDED WITH MAIN PLAN PERMIT # | | | 02011116 WERE NOT REVIEWED FOR CODE | | | COMPLIANCE FOR HOOD OR SUPPRESSION | | | SYSTEM. SEPARATE PLANS AND PERMIT ARE | | | REQUIRED FOR HOOD PERMIT APPLICATION. | | | SEPARATE PERMIT AND PLANS ARE REQUIRED | | | FOR FIRE SUPPRESSION SYSTEM FOR HOOD. |
|