Plan Review Notes
Plan Review Notes For Permit 02071887
Permit Number 02071887
Review Stop M
Sequence Number 1
Notes
Date Text
2002-08-22 00:00:00DENIED
 PROVIDE FULL PLANS AND INFORMATION ON
 HOOD. HOOD SHALL BE UL LISTED (PROVIDE
 SPECIFICS) OR ENGINEERED TO COMPLY WITH
 NFPA 96 AND 1997 SMC.
 PROVIDE INFORMATION ON DUCT WORK
 INCLUDING SHAFT IF STRUCTURE IS
 UNPROTECTED CONSTRUCTION.
 PLANS INCLUDED WITH MAIN PLAN PERMIT #
 02011116 WERE NOT REVIEWED FOR CODE
 COMPLIANCE FOR HOOD OR SUPPRESSION
 SYSTEM. SEPARATE PLANS AND PERMIT ARE
 REQUIRED FOR HOOD PERMIT APPLICATION.
 SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR FIRE SUPPRESSION SYSTEM FOR HOOD.