2002-07-30 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE ANY NECESSARY CHANGES
 IN THE PLANS AND RESUBMIT FOR REVIEW:
  
 1} THERE IS A MAIN DISCONNECT SHOWN ON
 THE RISER DIAGRAM, BUT NOT LOCATED ON
 THE DRAWING.PLEASE INDICATE LOCATION.
  
 2} THE LOCATION OF THE PANEL IN THE
 KITCHEN IN RELATIONSHIP TO THE
 AHU/EWH,IS IN VIOLATION OF 110-26,AND
 MUST BE CORRECTED TO COMPLY.
  
 3} THE LOCATION OF THE A/C CONDENSER
 DISCONNECT AS DRAWN IS IN VIOLATION OF
 110-26.
  
 4} PLEASE NOTE THE REQ`D BATH(S)
 CIRCUIT(S), PER 210-11-C-3,
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} PLEASE NOTE IF LOW VOLTAGE IS TO BE
 INSTALLED WITH THIS PERMIT, IT MUST BE
 SHOWN ON THE PLANS.
  
 7} PLEASE SHOW HOW THE VALUATION FOR
 PERMIT LISTED VALUE WAS ARRIVED PER
 104.6.5(ATTACHED).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  