| Plan Review Notes For Permit 02071681 |
| Permit Number |
02071681 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-02 00:00:00 | *************** UNSAT **************** | | | | | | PLEASE NOTE THAT AS PER FEILD INSPECTION | | | VALUE OF JOB EXCEEDS SUBMITTED APPLIED | | | VALUE. | | | PLEASE ALSO NOTE THAT A CORRECTION | | | NOTICE WAS ISSUED FOR ELECTRICAL DEMO | | | AND TEMP POWER FOR CONSTRUCTION. | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR THE ENTIRE SERVICE AND A BREAK | | | DOWN ON EACH "MAINS" LOAD. SHOW EXISTING | | | SERVICE ENTRANCE CONDUCTORS, SIZE AND | | | TYPE. PLEASE NOTE THAT PER FIELD | | | INSPECTION, CONDUCTOR AT POINT OF | | | SERVICE HAS INSULATION DETERIORATING. | | | PLEASE NOTE EXTENT OF WORK IN BLDG HAS | | | FAR EXCEEDED ANY % FOR BRINGING UP TO | | | CODE. PLEASE NOTE THAT SERVICE HAS | | | MORETHAN 8' OF UNPROTECTED CONDUCTORS | | | INSIDE THE BLDG.230-70 | | | PLEASE NOTE THAT MAIN ELECTRICAL ROOM | | | NEEDS TO BE LOCKED AND ONLY OPENED FOR | | | QUALIFIED PERSONNEL. PLEASE NOTE FIRE | | | RATING FOR MAIN ELECTRICAL ROOM TO BE | | | 1 HR RATING. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|