| Plan Review Notes For Permit 02071681 |
| Permit Number |
02071681 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-02 00:00:00 | 1) EXISTING STAIR TOWER LOCATED ON | | | SOUTH SIDE OF BUILDING REQUIRES | | | EMERGENCY LIGHTING. | | | | | | 2) NEW FIRE ESCAPE CONNECTION ON THE | | | NORTH SIDE IS REQUIRED TO BE COMPLETED, | | | INSPECTED AND APPROVED PRIOR TO | | | RECEIVING A C OF O. | | | | | | 3) CLOSET DOORS SWING TOO FAR INTO | | | CORRIDOR. | | | | | | 4) THE CORRIDOR IS REQUIRED TO BE AT | | | LEAST ONE HOUR FIRE RATED WITH RATED | | | OPENING PROTECTIVES EQUIPPED WITH | | | SELF-CLOSING DEVICES. THIS REQUIREMENT | | | MUST BE MET SINCE NO FIRE SPRINKLER | | | PROTECTION IS PRESENT WITHIN IT. | | | | | | 5) SEPARATIONS BETWEEN TENANTS MUST | | | COMPLY WITH BUILDING CODE REQUIREMENTS. | | | | | | 6) PORTABLE FIRE EXTINGUISHERS ARE | | | REQUIRED. | | | | | | 7) ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING ARE REQUIRED FOR TENANT | | | SPACES. | | | | | | 8) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE ALARM SYSTEM. IT IS NOT KNOWN | | | IF EXISTING SYSTEM IS OPERATIONAL. | | | | | | 9) THE ELEVATOR SHAFTS ARE TO BE | | | MARKED "SHAFTWAY" IN SIX HIGH LETTERS | | | ON A WHITE BACKGROUND. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|