| Date |
Text |
| 2002-11-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) COVER SHEET INDICATES WAREHOUSE AND |
| | SHOWROOM. PLEASE SHOW SQUARE FOOTAGE FOR |
| | OFFICE, WAREHOUSE, AND SHOWROOM INDIVID- |
| | UALLY. PLEASE INDICATE PRODUCT THAT WILL |
| | BE ON SALES ROOM FLOOR AND WAREHOUSE. |
| | 2) RPZ BACKFLOW IS REQUIRED ON WATER |
| | SERVICE TO BLDG. |
| | 3) PLEASE SUBMIT CALCULATIONS FOR MINIM- |
| | UM FACILITIES PER TABLE 403.1, AND TABLE |
| | 1003.1 (BLDG CODE). SHOW NUMBER OF PER- |
| | SONS REQUIRED FOR EACH OCCUPANCY. |
| | 4) WHAT WILL BULL PEN BE USED FOR? |
| | 5) PLEASE SUBMIT DETAILS FOR SHOWERS IN |
| | #104, 105, & 126. SEE SECTION 11-4.21 |
| | SHOWER STALLS. SHOW COMPLIANCE FOR ALL |
| | SUBSECTIONS, 4.21.2 SIZE/CLEARANCES, |
| | 4.21.3 SEAT, 4.21.4 GRAB BARS, 4.21.5 |
| | CONTROLS, 4.21.6 SHOWER UNIT, 4.21.7 |
| | CURBS. FIGURS 35(A) OR (B), & FIGURE |
| | 57(A) OR (B) |
| | 6) SHTS 3.1 OF 11 AND 3.2 OF 11, P/T |
| | FROM WATER HEATERS SHALL DRAIN TO A |
| | FLOOR SINK. FLOOR DRAIN ARE NOT AN APPRO |
| | VED INDIRECT WASTE RECEPTOR. |
| | 7) SHT 3.2 OF 11, SANITARY AND WATER |
| | RISER DIAGRAMS DO NOT REFLECT THE FLOOR |
| | PLAN. URNALS ARE ON WALL BEHIND MOP SINK |
| | NOT ON THE OTHER SIDE OF ROOM. W/C'S AND |
| | LAVS. MISSING OFF BOTH RISERS. WATER |
| | HAMMER ARRESTOR LOCATION SHALL BE NEAR |
| | THE FIXTURE IN AN "EFFECTIVE RANGE NOT |
| | AT THE TOP OF RISER IN CEILING PER PDI- |
| | WH 201 AND MANUFACTURE INSTALLATION IN- |
| | STRUCTIONS. WATER HAMMER ARRESTORS ARE |
| | REQUIRED PER 604.9. AIR CHAMBERS ARE NOT |
| | APPROVED. |
| | 8) SHT 3.2 OF 11 WATER RISER DIAGRAM, |
| | WATER PIPING TO WATER HEATER BY MOP SINK |
| | NOT SHOWN ON RISER. |
| | 9) THERMAL EXPANSION CONTROL REQUIRED |
| | PER 607.3 AND 607.3.2. PLEASE GIVE DE- |
| | TAIL. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |