| Plan Review Notes For Permit 02071609 |
| Permit Number |
02071609 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-10-30 00:00:00 | DENIED: | | | | | | 1.PLEASE PROVIDE EQUIPMENT SCHEDULE | | | ON PLAN. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | 3.PLEASE INDICATE DUCT SMOKE DETECTORS | | | AS PER 2001 FBC(M) 606.2.1 & 606.2.2 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|