| 2002-08-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) SHT A-1 ROOM 106 PRIVATE BATHROOM, |
| | PLEASE SHOW DETAILS FOR SHOWER. BACKING |
| | REQUIRED FOR GRAB BARS, AND SEAT FOR |
| | SHOWER. CURB TO BE MAX 1/2", CONTROLS |
| | SHALL BE WITHIN 38" TO 48" OFF FLOOR, |
| | SHOW WHICH WALL CONTROL AND SHOWER HEAD |
| | ARE ON. LAV SHALL HAVE A REMOVABLE VANI- |
| | TY OR BE CENTERED (2') ON THE 48"X30" |
| | CLEAR FLOOR SPACE. (PARALLEL APPROACH) |
| | PLEASE PROVIDE DETAILS FOR ADAPTABLE |
| | BATHROOM. 11-4.21 & ALL SUBSECTIONS |
| | 2) SHT A-1 BOTTLED WATER COOLER SHALL |
| | COMPLY WITH ARI-1010. PLEASE PROVIDE |
| | MANUF. INFORMATION. |
| | 3) SHT A-6.1 SANITARY RISER DIAG. FIX- |
| | TURES IN ROOM #114 (HDCP W/C, JANITOR |
| | SINK, URNALS, ECT SHALL NOT DRAIN INTO |
| | THE VENT FOR THE W/C IN THE FIRST STALL. |
| | PLEASE DRAIN THESE FIXTURES DOWNSTREAM |
| | OF THE VENT FOR THAT W/C. ALSO CHANGE |
| | SHT A-5 FLOOR PLAN. |
| | 4) SHT A-6.1 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT AT |
| | THE TOP OF DROPS AS SHOWN. PDI-WH 201 |
| | AND MANUF. INSTALL. INSTRUCTIONS. |
| | |
| | REVIEW BY KEN STEVENS |