| 2002-08-12 00:00:00 | PLEASE PROVIDE A PROPERTY SURVEY.ON |
| | THE SITE PLAN SHOW THE DIMENSIONS |
| | BETWEEN BUILDINGS, CONSTRUCTION TYPE OF |
| | EXISTING BUILDINGS AND THE PERCENTAGE |
| | OF OPENINGS IN THE EXTERIOR WALLS SO |
| | THAT COMPLIANCE WITH FBC TABLE 600 MAY |
| | BE DETERMINED.SEE ALSO, THE MINIMUM |
| | PLAN REVIEW CRITERIA CONTAINED IN FBC |
| | 104.3.1.1 AND 104.2.4. |
| | |
| | DETAIL 1 ON SHEET A-108, AND ELSEWHERE, |
| | INDICATE THE USE OF PLYWOOD IN THE |
| | EXTERIOR WALL ASSEMBLIES WHICH IS TYPE |
| | VI CONSTRUCTION.THIS CONSTRUCTION TYPE |
| | IS NOT PERMITTED IN THE DESIGNATED FIRE |
| | DISTRICT.SEE FBC APPENDIX A FBC 102.1 |
| | AS AMENDED BY THE CITY, AND REVISE AS |
| | NECESSARY. |
| | |
| | THE FRITTED GLASS IN THE ENTRANCE CANOPY |
| | MUST COMPLY WITH FBC 2405.3.2.1. |
| | |
| | PLEASE PROVIDE INFORMATION ON THE "ALUCO |
| | BOND PANELS" AND THE "AERO LITE SUN |
| | SHADE".SEE FBC 104.2. |
| | |
| | SHOW THE DESIGN LOAD FOR THE MEZZANINE |
| | ABOVE THE MEN'S LOCKER ROOM AND EGRESS |
| | REQUIREMENTS COMPLYING WITH FBC |
| | 1005.7.3. |
| | |
| | SHOW THE FIRE RATED SEPARATION BETWEEN |
| | THE SERVICE AREA AND THE SHOWROOM, |
| | GROUPS S AND B, IN ACCORDANCE WITH FBC |
| | 411.5. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO THE |
| | COUNTY, THE PERMIT PLANS STAMPED BY |
| | THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |