Plan Review Notes
Plan Review Notes For Permit 02071593
Permit Number 02071593
Review Stop P
Sequence Number 1
Notes
Date Text
2002-08-10 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT #1 GENERAL NOTES: #6 PLUMBING
 CONTRACTOR RESPONSIBLE FOR 2" WASTE NOT
 GENERAL CONTRACTOR. WASTE SHALL BE PIPED
 TO SANITARY NOT STORM. ALL DRAINS AND
 WASTE TO SANITARY AND OVERFLOW SHALL
 DRAIN TO STORM.
 2) SHT #1 GENERAL NOTES: #7 PLUMBING
 CONTRACTOR SHALL BE RESPONSIBLE FOR 1"
 POTABLE WATER NOT GENERAL CONTRACTOR.
 A BACKFLOW PREVENTER IS REQUIRED FOR
 WATER SERVICE TO FOUNTAIN.
 3) PLUMBING PERMIT IS REQUIRED.
 4) SHT #4 NON-ELECTRIC EQUIPMENT: (ED)
 4" FLOOR DRAIN TO SANITARY SEWER NOT
 FOUND.
 5) SHT #4 GENERAL NOTES: #'S 5, 6, 7, &
 8 ALL REFER TO GENERAL CONTRACTOR BEING
 RESPONSIBLE FOR PLUMBING CONTRACTOR WORK
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377