| Plan Review Notes For Permit 02071593 |
| Permit Number |
02071593 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-10 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SHT #1 GENERAL NOTES: #6 PLUMBING | | | CONTRACTOR RESPONSIBLE FOR 2" WASTE NOT | | | GENERAL CONTRACTOR. WASTE SHALL BE PIPED | | | TO SANITARY NOT STORM. ALL DRAINS AND | | | WASTE TO SANITARY AND OVERFLOW SHALL | | | DRAIN TO STORM. | | | 2) SHT #1 GENERAL NOTES: #7 PLUMBING | | | CONTRACTOR SHALL BE RESPONSIBLE FOR 1" | | | POTABLE WATER NOT GENERAL CONTRACTOR. | | | A BACKFLOW PREVENTER IS REQUIRED FOR | | | WATER SERVICE TO FOUNTAIN. | | | 3) PLUMBING PERMIT IS REQUIRED. | | | 4) SHT #4 NON-ELECTRIC EQUIPMENT: (ED) | | | 4" FLOOR DRAIN TO SANITARY SEWER NOT | | | FOUND. | | | 5) SHT #4 GENERAL NOTES: #'S 5, 6, 7, & | | | 8 ALL REFER TO GENERAL CONTRACTOR BEING | | | RESPONSIBLE FOR PLUMBING CONTRACTOR WORK | | | PLEASE CLAIRFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|