Date Text
2002-09-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1 LAV SHALL BE A MINIMUM OF 15"
 OFF THE WALL TO CENTER OF FIXTURE. A MIN
 IMUM OF 30" IS REQUIRED FROM THE CENTER
 OF THE WATER CLOSET TO THE CENTER OF THE
 ADJACENT FIXTURE (LAV). THE MINIMUM WID-
 TH OF THE TOILET ROOM SHALL BE 5'3"
 SEC 405.3.1 - 5'0" IS SHOWN FOR TOILET
 ROOM. PLEASE ADJUST PLANS.
 2) SANITARY RISER DIAGRAM STILL HAS A
 HORIZONTAL DRY VENT AT THE W/C WHICH IS
 NOT APPROVED (SEC 905.3). HAND SINK
 SHALL NOT DRAIN THROUGH THE WET VENTED
 SYSTEM , SEC 909.1. THE HAND SINK SHALL
 BE DRAINED DOWNSTREAM OF WET VENTED SYS.
 PLEASE SEE ATTACHED SHEET FROM PREVIOUS
 REVIEW FOR AN EXAMPLE OF AN APPROVED
 RISER DIAGRAM.
 3) PLEASE REMOVE VOIDED SHEETS AND RE-
 PLACE WITH NEW SUPERSEDED SHEETS.
  
 REVIEW BY KEN STEVENS