| Notes |
| Date |
Text |
| 2002-09-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A-1 LAV SHALL BE A MINIMUM OF 15" | | | OFF THE WALL TO CENTER OF FIXTURE. A MIN | | | IMUM OF 30" IS REQUIRED FROM THE CENTER | | | OF THE WATER CLOSET TO THE CENTER OF THE | | | ADJACENT FIXTURE (LAV). THE MINIMUM WID- | | | TH OF THE TOILET ROOM SHALL BE 5'3" | | | SEC 405.3.1 - 5'0" IS SHOWN FOR TOILET | | | ROOM. PLEASE ADJUST PLANS. | | | 2) SANITARY RISER DIAGRAM STILL HAS A | | | HORIZONTAL DRY VENT AT THE W/C WHICH IS | | | NOT APPROVED (SEC 905.3). HAND SINK | | | SHALL NOT DRAIN THROUGH THE WET VENTED | | | SYSTEM , SEC 909.1. THE HAND SINK SHALL | | | BE DRAINED DOWNSTREAM OF WET VENTED SYS. | | | PLEASE SEE ATTACHED SHEET FROM PREVIOUS | | | REVIEW FOR AN EXAMPLE OF AN APPROVED | | | RISER DIAGRAM. | | | 3) PLEASE REMOVE VOIDED SHEETS AND RE- | | | PLACE WITH NEW SUPERSEDED SHEETS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|