| Plan Review Notes For Permit 02071506 |
| Permit Number |
02071506 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) NEW TOILET ROOM SHALL BE ACCESSIBLE | | | SHOW ALL DETAILS FOR GRAB BARS, W/C, LAV | | | TURNING RADIUS ECT. PER 11-4.22 AND ALL | | | SUB SECTIONS. | | | 2) HAND SINK NOT SHOWN ON SANT RISER | | | DIAGRAM. | | | 3) FLOOR DRAIN AND LAV NOT VENTED. | | | 4) HORIZONTAL DRY VENT NOT ALLOWED. | | | SECTION 905.3 | | | 5) ALL SHEETS SHALL BE SIGNED AND SEALED | | | BY THE ARCHITECT. 61G1-16.003 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|