2002-07-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT DP 01 DEMO & REMOVE BLDG. IS
 THERE PLUMBING IN BLDG? IF SO A PLBG.
 PERMIT WILL BE REQUIRED FOR DEMO.
 2) SHT IP 03 A RAIN SENSOR IS REQUIRED
 AT CONTROL AND PUMP STATION. SEPARATE
 IRRIGATION PERMIT REQUIRED.
 3) SHT AA 02 PLEASE PROVIDE CALCULATIONS
 FOR DOWN SPOUTS AND SHOW SIZE OF DOWN
 SPOUTS.
 4) BACK FLOWS ARE REQUIRED FOR WATER
 SERVICE FOR EACH BUILDING SERVICED WITH
 POTABLE WATER. REDUCED PRESSURE ZONE
 5) SHT AMK 01 MARKET PLACE, PLEASE SUB-
 MIT A SANITARY & WATER RISER DIAGRAM.
 6) SHT AMK 05 DETAIL #3, WATER CLOSET
 SHALL BE 1'6" OFF WALL TO CENTER OF
 FIXTURE. PLEASE SHOW ON DETAIL.
 7) SHT AMK 05 SHOWER STALL DETAIL TO
 COMPLY WITH 11-4.21.7. CURBS SHALL BE NO
 HIGHER THAN 1/2". PLEASE SHOW ON DETAIL
 8) SHT AMK 06 DRAIN FOR EMERGENCY SHOWER
 SHALL DRAIN TO STORM AT WATER TOWER.
 9) SHT AMT 01 NO WATER OR SANITARY SHOWN
 ON UTILITY SITE PLAN FOR MARMOSET NIGHT-
 HOUSE.
 10) SHT A0 01 OBSERVATORY, SANITARY &
 WATER RISER DIAGRAM REQUIRED. PLEASE
 PROVIDE.
 11) SHT A0 01 SHOWS PLANTER DRAINS, BUT
 SHT A0 02 DETAIL SAYS STORM DRAINS.
 PLEASE CLAIRFY. PLEASE SHOW SIZE OF
 DRAINS AND SHOW WHERE THEY TERMINATE.
 12) SHT AS 01 PLEASE PROVIDE A SANITARY
 & WATER RISER DIAGRAM FOR PRIMATE NIGHT-
 HOUSE.
 13) SHT AT 01 WILL THE NELSON WATERS
 BE PIPED DIRECTLY? IF SO PLEASE PROVIDE
 A WATER RISER DIAGRAM FOR THE TAPIR/
 LLAMA/CAPYBARA NIGHTHOUSE.
  
 REVIEW BY KEN STEVENS