| Plan Review Notes For Permit 02071382 |
| Permit Number |
02071382 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-20 00:00:00 | | | | | | | 1.AS PER 2001 FBC(M) 306.5, WHERE | | | EQUIPMENT REQUIRING ACCESS ARE | | | INSTALLED ON ROOFS OR ELEVATED | | | STRUCTURES AT A HEIGHT EXCEEDING | | | 16 FT, SUCH ACCESS SHALL BE PROVIDED | | | BY A PERMANENT APPROVED MEANS OF | | | ACCESS.SUCH ACCESS SHALL NOT | | | REQUIRE CLIMBING OVER OBSTRUCTIONS | | | GREATER THAN 30". | | | | | | 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|