| Plan Review Notes For Permit 02071382 |
| Permit Number |
02071382 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-08-09 00:00:00 | 1) FIRE VEHICLE TURN-AROUND NOTED ON | | | PAGE GP04 TO COMPLY WITH NFPA 1, 2000 | | | EDITION. | | | | | | 2) GATES THAT FIRE AND PARAMEDICAL | | | EQUIPMENT ARE EXPECTED TO USE SHALL BE | | | AT LEAST TWENTY (20) FEET IN CLEAR | | | WIDTH. | | | | | | 3) ALL NEW STAIRS AND RAMPS ARE REQUIRED | | | TO BE EQUIPPED WITH HANDRAILS. | | | | | | 4) PROVIDE FLAMESPREAD DETAILS ON THE | | | THATCHED ROOF, SCAFFOLD TENT STRUCTURE, | | | MARKETPLACE BUILDING EXHIBITS. | | | | | | 5) PLEASE INDICATE LOCATIONS OF | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | 6) ARE PERSONS EXPECTED TO USE THE | | | OUTSIDE STEPS ON MAYAN RUIN. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|