| Plan Review Notes For Permit 02071311 |
| Permit Number |
02071311 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-25 00:00:00 | 1) PLANS DO NOT INDICATE THAT THE | | | KITCHEN FIRE SUPRESSION SYSTEM WILL BE | | | CONNECTED TO THE FIRE ALARM SYSTEM AS | | | REQUIRED BY CODE. | | | 2) MENS ROOM DISPLAYS A HORN STROBE AND | | | THE WOMENS ROOM DISPLAYS A STOBE. | | | ELIMINATE THE HORN IN THE MENS ROOM. | | | 3) PLANS FAIL TO INDICATE ANY DEVICES | | | NOTED FOR THE ELEVATOR AND THE PERTINENT | | | ELEVATOR MECHANICAL ROOM. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096, EXT. 8497 | | | 835-2910 |
|