Plan Review Notes
Plan Review Notes For Permit 02071105
Permit Number 02071105
Review Stop E
Sequence Number 4
Notes
Date Text
2005-09-23 00:00:00********** UNSAT **********
  
 1)NOTE:PLEASE ADDRESS NOTES FROM
 "PROVISO" WHICH WAS GIVEN ON DECEMBER
 17, 2002.
  
 2)NOTE: PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 215.5
  
 3)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS. THE CIRCUIT
 FEEDING THESE SHALL BE THE LOCAL BRANCH
 CIRCUIT FEEDING THAT AREA.
  
 4)NOTE: PLEASE SEE A "TYPICAL" PANEL
 SCHEDULEAND LOAD CALCULATIONS WAS
 SUBMITTED, HOWEVER UNITS ARE NOT THE
 SAME SIZE, DO NOT CONTAIN THE SAME ITEMS
 ETC.
 PLEASE SEE 220.3,220.10,220.11 ETC
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%.
 215.3,230.42
  
 5)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR
 PANELS. PLEASE CALRIFY 10-"A""C"??
 PLEASE ALSO SEE VOLTAGE IS SHOWN AS
 120/480V ??
  
 6)NOTE: PLEASE SEE SHOW WINDOW CIRCUITS
 ARE SHOWN ON PANEL SCHEDULE, HOWEVER
 THESE ARE NOT SHOWN ON PLANS.?
 210.62, 220.12
  
 7)NOTE: PLEASE SEE 600.5 FOR MISSING
 SIGN CIRCUIT.
  
 8)NOTE: PLEASE INDICATE OCCUPANCY ON
 PLANS.
  
 9)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
 PLEASE SEE ORIGINAL PLANS CALLED FOR 2/0
 MIN, HOWEVER RISER HAS NOW BEEN REVISED
 TO LARGER SEC'S AND SMALLER GEC.
 PLEASE SEE A 2/0 MIN IS REQUIRED AS
 SHOWN ON ORIGINAL PLANS.
  
 10)NOTE: PLEASE CORRELATE SIZING OF
 PANELS ON RISER. ONE SHOWS 150A AND THE
 OTHER 200A.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  