| 2005-09-23 00:00:00 | ********** UNSAT ********** |
| | |
| | 1)NOTE:PLEASE ADDRESS NOTES FROM |
| | "PROVISO" WHICH WAS GIVEN ON DECEMBER |
| | 17, 2002. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUTING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | TO BE SUBMITTED. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS. THE CIRCUIT |
| | FEEDING THESE SHALL BE THE LOCAL BRANCH |
| | CIRCUIT FEEDING THAT AREA. |
| | |
| | 4)NOTE: PLEASE SEE A "TYPICAL" PANEL |
| | SCHEDULEAND LOAD CALCULATIONS WAS |
| | SUBMITTED, HOWEVER UNITS ARE NOT THE |
| | SAME SIZE, DO NOT CONTAIN THE SAME ITEMS |
| | ETC. |
| | PLEASE SEE 220.3,220.10,220.11 ETC |
| | PLEASE SEE ALL CONTINUOUS LOADS ARE TO |
| | BE SHOWN AT 125%. |
| | 215.3,230.42 |
| | |
| | 5)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR |
| | PANELS. PLEASE CALRIFY 10-"A""C"?? |
| | PLEASE ALSO SEE VOLTAGE IS SHOWN AS |
| | 120/480V ?? |
| | |
| | 6)NOTE: PLEASE SEE SHOW WINDOW CIRCUITS |
| | ARE SHOWN ON PANEL SCHEDULE, HOWEVER |
| | THESE ARE NOT SHOWN ON PLANS.? |
| | 210.62, 220.12 |
| | |
| | 7)NOTE: PLEASE SEE 600.5 FOR MISSING |
| | SIGN CIRCUIT. |
| | |
| | 8)NOTE: PLEASE INDICATE OCCUPANCY ON |
| | PLANS. |
| | |
| | 9)NOTE: PLEASE SEE MIN GROUNDING |
| | ELECTRODE CONDUCTOR PER 250.66. |
| | PLEASE SEE ORIGINAL PLANS CALLED FOR 2/0 |
| | MIN, HOWEVER RISER HAS NOW BEEN REVISED |
| | TO LARGER SEC'S AND SMALLER GEC. |
| | PLEASE SEE A 2/0 MIN IS REQUIRED AS |
| | SHOWN ON ORIGINAL PLANS. |
| | |
| | 10)NOTE: PLEASE CORRELATE SIZING OF |
| | PANELS ON RISER. ONE SHOWS 150A AND THE |
| | OTHER 200A. |
| | 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |