| Plan Review Notes For Permit 02071105 |
| Permit Number |
02071105 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-12-18 00:00:00 | *************** PROVISO/NOTES ********* | | | | | | 1)NOTE: PLEASE SUBMIT ONLY ONE LOAD | | | CALCULATION. NEW ATTACHED SHEETS HAVE | | | TWO. | | | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | | PLANS AND CORRELATE WITH A SUBMITTED | | | PANEL SCHEDULE. PLEASE ALSO NOTE | | | CIRCUITING FOR EM/EXT LTS TO CONFORM | | | TO 700-12E. | | | | | | 3)NOTE: PLEASE SHOW ACTUAL LOCATIONS | | | OF EM/EXT FIXTURES.. | | | | | | PLEASE SUBMIT THE ABOVE REVISION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|