Plan Review Notes
Plan Review Notes For Permit 02071105
Permit Number 02071105
Review Stop B
Sequence Number 3
Notes
Date Text
2006-01-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02071105
 ADD: 539 OGSTON ST
 CONT: H. CANO
 TEL: (561)543-1290
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW / REVISION
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) THIS PERMIT WAS LET AS A SHELL PERMIT
 AND FOR SINGLE TENANT.UPDATE VALUE OF
 PERMIT IF TENANT BUILD OUT IS TO BE PART
 OF THIS PERMIT.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE INCOMPLETE FOR A TENANT BUILD
 OUT:
 A) BAY # 1 NO REST ROOM.
  
 B) BAY # 2&3 BOTH INDICATE DOOR OPENINGS
  
 BUT NO INFORMATION AS TOO DOOR SWING FOR
 INTERIOR OR EXTERIOR DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 C) PLANS INDICATE USE OF FIRE STOPPING
 MATERIALS (A& B). PLEASE PROVIDE THE
 TECHNICAL SHEETS OF THE ACTUAL SYSTEM TO
 BE USED.
 705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
 PROVIDE A FLEXIBLE SEALANT AT THE
 WALL/ ROOF DECK DETAILING SYSTEM TO BE
 USED.
  
 D) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 E) INSPECTION HISTORY INDICATES A
 FAILURE NEEDS FOR INFORMATION FOR GARAGE
 DOOR ANCHOR DETAILS.
  
 F) PLANS DO NOT INDICATE IF THE BATHROOM
  
 AND OFFICE WALLS ARE TO CONTINUE TO THE
 ROOF DECK ABOVE? PLANS DO NOT INDICATE
 A CEILING ASSEMBLY TYPE FOR THE OFFICE
 NOR THE RESTROOMS.
  
 G) PLANS ONLY PROVIDE INFORMATION ON THE
  
 FIRE RATED WALL, PLANS INDICATE USE OF
 WOOD STUDS FOR THE OFFICE AND RESTROOM
 PARTITIONS, DOES THE STUDS CONTINUE TO
 THE ROOF DECK? IF NOT ," NOTE" SIGNAGE
 MUST BE PROVIDED INDICATINGAREA ABOVE
 IS NOT TO BE USED FOR STORAGE. IF
 STORAGE IS AN OPTION PROVIDE THE
 FOLLOWING INFORMATION:
 106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 H) IS THE OFFICE TO BE AIR CONDITIONED?
  
 I) ELECTRICAL PLANS WILL NEED TO BE UP
 DATED TO SHOW THE NEW LAY OUT, NEW
 OFFICE, AND EXIT LIGHTING.
  
 J) PLANS ALSO NEED TO INDICTE THE
 OCCUPANCY FOR EACH SPACE? IF DIFFERENT
 OCCUAPNCIES MAY REQUIRE MORE THAN A 1 HR
 RATED WALL. SEE TABLE 704.1.
  
 ADDITIONAL COMMENTS MAY OCCUR ON THE
 NEXT REVIEW DEPENDING ON THE ANSWERS TO
 THIS REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved