Plan Review Notes
Plan Review Notes For Permit 02071105
Permit Number 02071105
Review Stop M
Sequence Number 2
Notes
Date Text
2002-11-21 00:00:00DENIED:
  
 PLEASE PROVIDE INFORMATION ON
 VENTILATION.INDICATE SEQUENCE OF FANS
 SHOWN ON PLAN SHEET A.2 (FANS RUN
 CONTINUOUSLY OR JUST WHEN OVERHEAD
 DOOR IS OPEN? INDICATE AIR MAKE-UP
 SHOULD OVERHEAD DOOR BE CLOSED.)
  
 INDICATE OUTSIDE AIR REQUIREMENT IN
 ACCORDANCE WITH 2001 FBC(M) TABLE 403.3
 OR ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.