| 2002-09-16 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE PANEL SCHEDULE |
| | MENTION SHOW WINDOWS AND SIGN CIRCUITS, |
| | BUT NOTHING SHOWNON PLANS? |
| | |
| | 2)NOTE: PLEASENOTE NO PANEL SCHEDULE |
| | SUBMITTED FOR HOUSE PANEL? |
| | |
| | 3)NOTE:PLEASE NOTE CIRCUITING NEEDS TO |
| | BE SHOWN ON PLANS AND CORRELATE WITH |
| | SUBMITTED PANELS. |
| | |
| | 4)NOTE: PLEASE SHOW LOCATION ON PLANS |
| | AND SHOW LOCATIONS OF PANELS IN EACH |
| | SPACE. IT IS NOTED THAT ONE PANEL IS |
| | SHOWN ON FLOOR PLAN BUT NONE OF THE |
| | OTHERS?? |
| | |
| | 5)NOTE: PLEASE NOTE/SEE FIRE REVIEW |
| | COMMENTS FOR EM/EXIT LTS. |
| | |
| | 6)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| | LOADS ARE TO BE SHOWN AT 125%. PER 215-3 |
| | 230-42 |
| | |
| | 7)NOTE: PLEASE NOTE THAT PLANS THAT ARE |
| | SIGNED AND SEALED BY AN ENGINEER ARE |
| | REQ`D BY FS/FAC TO HAVE A TITLE BLOCK |
| | PER 61G15-23.002. |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | 110-9/215-5 |
| | |
| | 9)NOTE: PLEASE CLARIFY WIRE SIZES FROM |
| | GUTTER TO MAINS/METER. |
| | |
| | 10)NOTE: PLEASE SHOW SIZE/TYPE GROUNDING |
| | ELECTRODE CONDUCTOR PER 250-50 AND |
| | SIZE PER 250-66. |
| | |
| | 11)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | TO CONFORM TO 220-3,220-10,220-11,220-13 |
| | PLEASE NOTE SERVICE IS NOTED TO HAVE |
| | 4 150A DISC`S AND 60A FOR HOUSE BUT |
| | HOUSE IS ALSO NOT SHOWN.? |
| | |
| | 12)NOTE: PLEASE SEE OTHER REVIEWERS |
| | COMMENTS IN REFERENCE TO OLD PLANS AND |
| | PERMIT #`S BEING SHOWN AND SUBMITTED |
| | THAT HAVE BEEN EXPIRED FOR MANY YEARS. |
| | PLEASE NOTE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE NOTE THAT PLANS ARE NOT |
| | COMPLETE FOR REVIEW AT PRESENT TIME |
| | AND MAY HAVE OTHER COMENTS WHEN PLANS |
| | ARE RE-SUBMITTED. PLEASE CALL IF THERE |
| | ARE ANY QUESTIONS. |
| | |