Plan Review Notes
Plan Review Notes For Permit 02071105
Permit Number 02071105
Review Stop B
Sequence Number 1
Notes
Date Text
2002-09-16 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02071105
 ADD: 539 OGSTON ST
 CONT: H CONS CONSTRUCTION
 TEL: (561)791-8763
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SURVEY RECOGNIZES THE WRONG CODE.
  
 2) SHEET# 1, NOT SIGNED OR SEALED, DATED
 DEC. 14, 1996 THIS WOULD BE THE REVIEWED
 UNDER THE 1994 STANDARD BUILDING CODE,
 WHY IS THIS PART OF THE PLAN?
  
 3) F 101.1.2 THIS LOT IS LOCATED IN THE
 "FIRE DISTRICT"
  
 4) F102.1 TYPES OF BUILDINGS ALLOWED IN
 A FIRE DISTRICT TYPE I, II, III, IV,
 & V. THIS PLAN INDICATES THAT THE EXIST-
 ING BUILDING IS A DUPLEX TYPE VI CON-
 STRUCTION,(CBS WALLS) WHICH IS IT?
  
 5) F 103.1 EXISTING BUILDINGS WITHIN THE
 FIRE DISTRICT. AN EXISTING BUILDING
 SHALL NOT HEREAFTER BE INCREASED UNLESS
 IT IS OF A TYPE CONSTRUCTION PERMITTED
 FOR NEW BUILDINGS WITHIN THE FIRE
 DISTRICT.
  
 6) F102.2.4 ROOF COVERINGS IN THE FIRE
 DISTRICT SHALL CONFORM TO REQUIREMENTS
 OF A CLASS A OR B ROOF COVERINGS AS
 DIFINED IN 1505.
  
 7) 301.2 OCCUPANCY OR USE: WHAT IS THE
 PROPOSED USAGE OF THIS BUILDING? DEPEND-
 ING ON THE USE STORAGE, HAZARDOUS, OR
 REPAIR GARAGE?
  
 8) F102.6 EXTERIOR WALLS OF TYPE IV
 BUILDINGS SHALL HAVE A FIRE RESISTANCE
 OF 2 HOURS OR MORE WHEN SUCH WALLS ARE
 LOCATED WITHIN 30 FT OF A COMMON PROPER-
 TY LINE OR AN SSUMED PROPERTY LINE .
 TABLE 600 TYPE V BUILDING ALSO REQUIRES
 2 HR RATED WALLS, ASSUMED PROPERTY LINE
 BETWEEN BUILDINGS ON SAME LOT.
  
 9) NORTH ELEVATION, SWING DOORS SHALL
 REQUIRE 1 1/2 HR OPENING PROTECTIVES,
 PER 705.1.1.2.
  
 10) FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 12)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) LARGE GARAGE DOOR 14' TALL
 B) ROOFING ASSEMBLIES
  
 13) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 14) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026