| Plan Review Notes For Permit 02071003 |
| Permit Number |
02071003 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-07-17 00:00:00 | PROVISO: | | | | | | 1. 2001 FBC 306.6 REQUIRES LEVEL | | | PLATFORM PROVIDED ON EACH SIDE OF THE | | | APPLIANCE AND NO LES 30 INCHES WIDE IN | | | ANY DIMENSION AND SHALL BE PROVIDED | | | WITH GAURDS PER 304.8. | | | | | | 2. IF ROOF HEIGHT OF EQUIPMENT EXCEEDS | | | 16' COMPLIANCE WITH 306.5 IS REQUIRED. | | | | | | 3. MANUFACTURES INSTALLATION | | | INSTRUCTIONS FOR CERAMIC BLANKET TO BE | | | ON SITE FOR INSPECTION. PROVIDE | | | INSPECTION OF WELDS PRIOR TO | | | CONCEALMENT. |
|