| 2002-07-17 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE NECESSARY CHANGES ON |
| | THE PLAN,AND RESUBMIT FOR REVIEW; |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} SHOW SERVICE CONDUCTORS AND SIZES TO |
| | METER. |
| | |
| | 3} SHOW LOCATION OF SUB-PANELS ON |
| | DRAWINGS.IF EITHER OF THE PANELS SERVES |
| | ANOTHER BUILDING OR STRUCTURE IT MUST |
| | COMPLY WITH 225-31/32 & 250-32. |
| | |
| | 4} THE WATER HEATER LISTED ON PANEL |
| | SCHEDULE (SUB-PANEL#2) HAS OCP OF 30 |
| | AMPS. |
| | THE LOAD CALCS SHOW THE HEATER @3000 |
| | VA,THIS DOES NOT COMPLY WITH ARTICLE |
| | 422-11(E)(3). |
| | |
| | 5} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 6} PLANS ARE NOT OF SUFFICIENT CLARITY |
| | TO DETERMINE COMPLIANCE WITH |
| | CODES.PLEASE REDRAW PER |
| | 104.2.1(ATTACHED). |
| | |
| | 7} PLEASE INDICATE THE COMPLETE SCOPE OF |
| | PROPOSED WORK,IS THIS A SERVICE |
| | CHANGE,OR DO PLANS INDICATE AN EXISTING |
| | SERVICE,IS THERE ANY WORK BEING DONE ON |
| | THE FIRST FLOOR? |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL; |
| | |