Date Text
2002-07-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 THE PLAN,AND RESUBMIT FOR REVIEW;
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} SHOW SERVICE CONDUCTORS AND SIZES TO
 METER.
  
 3} SHOW LOCATION OF SUB-PANELS ON
 DRAWINGS.IF EITHER OF THE PANELS SERVES
 ANOTHER BUILDING OR STRUCTURE IT MUST
 COMPLY WITH 225-31/32 & 250-32.
  
 4} THE WATER HEATER LISTED ON PANEL
 SCHEDULE (SUB-PANEL#2) HAS OCP OF 30
 AMPS.
 THE LOAD CALCS SHOW THE HEATER @3000
 VA,THIS DOES NOT COMPLY WITH ARTICLE
 422-11(E)(3).
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} PLANS ARE NOT OF SUFFICIENT CLARITY
 TO DETERMINE COMPLIANCE WITH
 CODES.PLEASE REDRAW PER
 104.2.1(ATTACHED).
  
 7} PLEASE INDICATE THE COMPLETE SCOPE OF
 PROPOSED WORK,IS THIS A SERVICE
 CHANGE,OR DO PLANS INDICATE AN EXISTING
 SERVICE,IS THERE ANY WORK BEING DONE ON
 THE FIRST FLOOR?
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  